On DIN Rail EN60715(35mm) by means of fast clip device
Connection
Power Supply in Both Directions
Tripping Current Range:
Lagging Angle
I△n>0.01A
I△n≤0.01A
0°
0.35I△n ≤ I△ ≤ 1.4I△n
0.35I△n ≤ I△ ≤ 2I△n
90°
0.25I△n ≤ I△ ≤ 1.4I△n
0.25I△n ≤ I△ ≤ 2I△n
135°
0.11I△n ≤ I△ ≤ 1.4I△n
0.11I△n ≤ I△ ≤ 2I△n
Alternative Current Sensitive
Pulsating Direct Current Sensitive
Surge Current Proof
B Class Tripping is ensured for sinusoidal AC residual currents pulsed DC residual current, alternating residual sinusoidal currents up to 1000Hz, pulsating direct residual currents and for smooth direct residual currents, whether applied suddenly or increasing slowly.
They react to AC and pulsating DC fault current which reach 0 or almost 0 within one time period of the mains frequency.
RCCB’s surge capacity. Not tripping at standardized 8/20 us surge-current waves acc.to VDE 0432 Part 2 with surge current values of up to 250A.
1、Application The NDQ3HP bypass automatic transfer switching equipment applies to the automatic transfer between two-way power supplies in the emergency power supply system with the AC rated working voltage of 415V and below, rated frequency of 5...
1. Applicable Scope and Purpose of Circuit Breaker The NDM2E-400 series of electronic molded case circuit breakers (hereinafter referred to as circuit breakers) apply to infrequent switching of circuits with the AC 50Hz, the working voltage of A...
1.Applicable Scope and Purpose The NDQ3-250 P-grade ATSE are applicable for sites with the AC voltage below AC380V.AC400V.AC415V and the rated frequency of 50Hz. This product complies with the GB14048.1-2012 and GB/T14048.11-2016 standards in acco...
1. Applicable Scope and Purpose of Circuit Breaker The NDM2L-125 molded case circuit breaker with the residual current protection (hereinafter referred to as circuit breaker) applies to infrequent switching of circuits with the AC 50/60Hz, the w...